Senseca
ELECTRA SCV Capacitive Level Switch
Capacitive level switch for liquids, powders and granular materials.
No moving parts, PTFE coated electrode
NPN output, 12…35 Vdc, max. load 3 W
DIN 43650 (IP65) or M12 (IP67) connection, lengths up to 1000 mm
Overview
The Senseca ELECTRA SCV is a capacitive level switch for controlling the level of liquids such as water, oil and gas, and solids such as powders and granular materials. With no moving parts, a PTFE coated electrode and hermetic polyurethane resin construction, it is designed for high operational reliability in difficult conditions such as those found on industrial plants.
It runs on 12…35 Vdc and switches an NPN output with a max. load of 3 W. Probes come in 50 or 90 mm lengths, up to 1000 mm on request, with a DIN 43650 (IP65) or M12 (IP67) connection. It handles pressures up to 50 bar and media temperatures from -30 to +125 °C.
Typical applications
Level control of water and conductive liquids
Level control of oil and non-conductive liquids
Powders and granular materials
Industrial plants
Process and automation systems
Key Features
Capacitive level switch for liquids, powders and granulates
No moving parts
PTFE coated Cu-Zn alloy electrode
Hermetic construction with polyurethane resin
NPN output, max. load 3 W
12…35 Vdc power supply, 5 mA consumption
DIN 43650 (IP65) or M12x1 (IP67) electrical connection
Probe lengths 50 or 90 mm, up to 1000 mm on request
Max. pressure 50 bar, media temperature -30…+125 °C
Custom activation delay (1…10 s) and differential (0…5 mm) on request
Benefits
High operational reliability in difficult industrial conditions
One sensor type for liquids and bulk solids
Minimal maintenance: periodic electrode check only
Flexible ordering: length, thread, material and connection to suit the application
Specifications
GENERAL |
|
Measuring principle | Capacitive |
Media | Liquids such as water, oil and gas; solids such as powders and granular materials |
Moving parts | None |
ELECTRICAL |
|
Power supply | 12…35 Vdc |
Current consumption | 5 mA |
Electrical output | NPN, max. load 3 W |
Output function (no level condition) | I2: active (ON); I1: deactive (OFF) |
Activation delay | 4 s (1…10 s on request) |
Differential | 3 mm (0…5 mm on request) |
ELECTRICAL CONNECTION |
|
S1 | DIN 43650 plug, IP65 |
S3 | M12x1, 4 poles, IP67 |
PROBE |
|
Electrode | Cu-Zn alloy |
Electrode coating | PTFE |
Length L0 | 50 mm, 90 mm; max. 1000 mm on request |
Switch point L1, vertical mounting | L0 - 10 ± 2 mm |
Switch point, horizontal mounting | On the axis of the probe |
Use / type of liquid | W: H₂O and conductive liquids; Z: oil and non-conductive liquids |
PROCESS CONNECTION |
|
DN 008 | 1/4" fitting, SW 24 mm, B 10 mm, A 74 mm, A1 58 mm |
DN 015 | 1/2" fitting, SW 24 mm, B 14 mm, A 74 mm, A1 58 mm |
Male thread | NPT conical; parallel UNI 228/1 and conical UNI 7/1 on request |
Materials | Brass; AISI-316 on request |
Housing diameter | Ø 29 mm |
OPERATING CONDITIONS |
|
Max. pressure | 50 bar |
Media temperature range | -30…+125 °C |
Protection degree | Minimum IP65 |
CONSTRUCTION |
|
Construction | Hermetic, polyurethane resin |
MAINTENANCE |
|
Maintenance | Periodic review of the electrode and its coating; if necessary, clean with non-corrosive liquids |
ORDERING CODE |
|
Example | SCV W 008 NO E50 I2 T S1 |
Structure | Type of liquid (W/Z), process connection size (008/015), thread and material, electrode coating and length, electrical output, delay/differential on request (T), electrical connection (S1/S3) |
Drawing

Downloads
| ELECTRA-SCV-Datasheet-EN | DownloadELECTRA-SCV-Datasheet-EN |
|---|
Related Products

Senseca
SEMS-2000 Solar Energy Measurement System
Compact 2-axis solar tracking system for automatic DNI, DHI and GHI monitoring with suitable sensors.
Learn More
Senseca
HDMCS-100 Compact Weather Station
Compact, self-powered automatic weather station for wind, temperature, humidity, pressure and rainfall monitoring.
Learn More
Senseca
GEO-MDFS2 Dust Fall Monitoring System
Dust fall monitoring system for PV panel cleaning decisions.
Learn More
Senseca
VNR 21/22 Conductive Level Signal Amplifier
Signal amplifier for SL series conductive level probes.
Learn More