VNR 21/22 Conductive Level Signal Amplifier


Signal amplifier for conductive level control with SL series probes.

  • 1-channel (VNR.2100) or 2-channel (VNR.2200) versions

  • SPDT relay output, 230 Vac 6 A, with front LED per channel

  • 10…250 µS sensitivity, DIN rail mounting

Quantity
1

Overview

The Senseca VNR 21/22 is a signal amplifier that works with SL series conductive probes to control the level of liquids. When the liquid touches the electrode, a relay inside the unit switches, so it can drive any alarm system or actuator. It measures with low potential alternating current, which avoids the electrode incrustation and tank perforation caused by direct current.

Choose the single-channel VNR.2100 or the two-channel VNR.2200. Each channel has an SPDT relay output (230 Vac, 6 A) and a front panel LED showing alarm status. Sensitivity covers 10…250 µS as standard, with 1…10 µS on request, and is set with a front panel trimmer from a factory setting of 20 µS. The ABS housing mounts on a 35 mm DIN rail.

Typical applications

  • Level control of conductive liquids with SL series probes

  • Min./max. level alarms

  • Automatic tank fill-up with pump control

  • Dosage and safety systems using multiple probes and control units

  • Control cabinet installation

Key Features

  • Interface for SL series conductive level probes

  • 1-channel (VNR.2100) or 2-channel (VNR.2200) versions

  • Low potential AC measurement avoids electrode incrustation and tank perforation

  • Sensitivity 10…250 µS, adjustable by front panel trimmer (1…10 µS on request)

  • Factory set to 20 µS

  • SPDT relay output per channel, 230 Vac, 6 A

  • Front panel LED alarm display per channel

  • Supplies the probes with 22 Vac

  • 24 / 230 Vac, 50/60 Hz power supply (110 Vac on request)

  • ABS housing for 35 mm DIN rail mounting, IP 40

Benefits

  • Reliable switching signal for level control

  • Reduced electrode wear compared with DC measurement

  • Can drive any alarm system or actuator via the relay

  • One or two control points from a single unit

  • Simple commissioning with factory setting and front trimmer

  • Clean integration in control cabinets

Specifications

GENERAL

 

Versions

VNR.2100: 1 channel; VNR.2200: 2 channels

Function

Interface (signal amplifier) for SL series conductive level probes

Measuring principle

Conductivity, using low potential alternating current

Input signal

From conductive probes (SL series)

 

 

SENSITIVITY

 

Sensitivity range

10…250 µS (1…10 µS on request)

Sensitivity adjustment

Front panel trimmer (VNR.2100: 1x; VNR.2200: 2x)

Factory setting

20 µS

 

 

OUTPUTS

 

Output relay

VNR.2100: SPDT, 230 Vac, 6 A; VNR.2200: 2 x SPDT, 230 Vac, 6 A

Alarm display

Front panel LED (VNR.2100: 1x; VNR.2200: 2x)

Power supply to probes

22 Vac

 

 

POWER REQUIREMENT

 

Power supply

24 / 230 Vac, 50/60 Hz (110 Vac on request)

Power consumption

VNR.2100: 5 VA; VNR.2200: 10 VA

 

 

ENVIRONMENTAL

 

Operating ambient temperature

-20…+50 °C

Protection degree

IP 40

 

 

MECHANICAL

 

Housing

ABS

Mounting

DIN rail (35 mm)

Dimensions

55 x 75 x 110 mm

Electrical connection

VNR.2100: 10 poles terminal board; VNR.2200: 20 poles terminal board

 

 

ORDERING CODE

 

Example

VNR.2100 10–250 µS 24/230VAC

Structure

One or two channels amplifier (VNR.2100 / VNR.2200), sensitivity (10–250 µS or 1–10 µS), power supply (24/230 Vac or 110 Vac)

Drawing

VNR-21-22-Dimensional-Drawing

Downloads