WETEC
ELECTRA SL Conductive Level Probe thumbnail 1
ELECTRA SL Conductive Level Probe thumbnail 2
ELECTRA SL Conductive Level Probe thumbnail 3

Senseca

ELECTRA SL Conductive Level Probe


Conductive level probe for industrial liquid control, from 1 µS.

  • Up to 4 coated electrodes, 500, 1000 or 1500 mm long

  • Works with ELECTRA VNR21.22 control units

  • DIN 43650 plug output, minimum IP65

Quantity
1

Overview

The Senseca ELECTRA SL is a conductive level probe that, together with ELECTRA VNR21.22 control units, controls the level of liquids with a minimum conductivity of 1 µS. Its hermetic, epoxy resin sealed construction and minimum IP65 protection are designed for high operational reliability in difficult conditions such as those found on industrial plants.

Each probe can have 1, 2, 3 or 4 coated electrodes, supplied in 500, 1000 or 1500 mm lengths and shortened during installation to suit the controlled level. Coatings come in Polyolefins, Kynar or PTFE, with a choice of process connection threads and materials. Electrical output is via a DIN 43650 plug, and the probe works up to 6 bar and 100 °C.

Typical applications

  • Liquid level control in industrial plants

  • Conductive liquids from 1 µS

  • Multi-level switching with up to 4 electrodes in one probe

  • Min./max. level alarms with VNR21.22 control units

  • Automatic tank fill-up with VNR21.22 control units

Key Features

  • Conductive level probe for liquids from 1 µS

  • Works with ELECTRA VNR21.22 control units

  • 1, 2, 3 or 4 electrodes per probe

  • Electrode lengths 500, 1000 or 1500 mm, shortened on installation

  • Coated electrodes: Polyolefins, Kynar or PTFE

  • Hermetic construction, epoxy resin sealed

  • DIN 43650 plug electrical output

  • Minimum IP65 protection

  • Max. 6 bar and 100 °C

  • Process connections from 3/8" to 1-1/2"

Benefits

  • High operational reliability in difficult industrial conditions

  • Several switching levels from a single probe

  • Electrode length adapted on site to the level being controlled

  • Wide choice of materials and process connections

  • Minimal maintenance: periodic electrode check only

Specifications

GENERAL

 

Measuring principle

Conductive

Minimum liquid conductivity

1 µS

Control unit

Works in combination with ELECTRA VNR21.22 electronic control units

Construction

Hermetic, epoxy resin sealed

 

 

ELECTRODES

 

Number of electrodes per probe

1, 2, 3 or 4

Electrode length L

500, 1000 or 1500 mm (shortened during installation as required)

Electrode coating

VL: Polyolefins; K: Kynar; E: PTFE

 

 

ELECTRICAL

 

Electrical output

S1: DIN 43650 plug

 

 

OPERATING CONDITIONS

 

Max. pressure

6 bar

Max. temperature

100 °C

Protection degree

IP65 (minimum)

 

 

PROCESS CONNECTION

 

DN 10

3/8" thread, SW 32 mm, A 63 mm, B 20 mm, 1 electrode

DN 15

1/2" thread, SW 32 mm, A 63 mm, B 20 mm, 1 or 2 electrodes

DN 25

1" thread, SW 40 mm, A 68 mm, B 20 mm, 3 electrodes

DN 40

1-1/2" thread, SW 55 mm, A 68 mm, B 20 mm, 4 electrodes

Male thread

G: parallel UNI 228/1; C: conical UNI 7/1 and N: conical NPT on request

Materials

P: polypropylene; B: nickel plated brass and S: AISI-316 on request

 

 

INSTALLATION AND MAINTENANCE

 

Installation

The ground electrode must always be the longest and always immersed in the liquid; after shortening, remove the coating from the terminal part for about 1 cm

Maintenance

Periodically check the condition of the electrodes and their coating; clean with non-aggressive liquids if needed

 

 

ORDERING CODE

 

Example

SL P 15G 2 x 1000 K S1

Structure

Process connection material, process connection dimension and thread, number and length of electrodes (mm), electrode coating, electrical output

Drawing

ELECTRA-SL-Dimensional-Drawing

Downloads

ELECTRA-SL-Datasheet-EN DownloadELECTRA-SL-Datasheet-EN