Senseca
OMNIPLUS-F Thermal Flow and Temperature Transmitter
Thermal flow and temperature transmitter for liquids
Calorimetric (thermal) measuring principle with no moving parts and no wear, measuring flow from 2...300 cm/s plus medium temperature, with an integrated volume meter with preset.
Fast response time of approx. 1-2 s in water (25 °C), with several sensor and process connection versions and an oil-filled option.
1.2 inch graphic LCD, IO-Link, 1 analog output and 2 configurable switching outputs in a waterproof all-metal housing, IP65 / IP67.
Overview
The Senseca OMNIPLUS-F is a flow transmitter for water and other liquids with integrated temperature measurement. It works on a calorimetric (thermal) principle, measures flow from 2...300 cm/s and has a fast response time.
It has a 1.2 inch graphic LCD, IO-Link, 1 analog output and 2 configurable switching outputs, and is built in a waterproof all-metal housing with a mineral glass front. Several sensor versions are available, from push-in sensors to threaded and sealing cone connections.
Typical applications
Flow measurement of water
Flow measurement of other liquids
Medium temperature measurement in liquids
Flow monitoring with limit switch, frequency or pulse outputs
Volume metering with preset counter
Installations with high air humidity and heavily fluctuating temperatures (oil-filled version)
Flow transmitter for water and other liquids with integrated temperature measurement
Measuring range 2...300 cm/s
Fast response time
Integrated volume meter with preset
Measuring method without moving parts, no wear
Wetted material stainless steel
1 analog output (20 mA / 10 V)
2 versatile configurable switching outputs
IO-Link interface
High-resolution graphic LCD
Parameters programmable with multifunction ring
Waterproof all-metal housing (IP67)
Mineral glass front, scratch-proof and chemically resistant
Benefits
No moving parts, so no wear
Fast response time, approx. 1-2 s in water (25 °C)
Flow and medium temperature measured by one device
Switching outputs configurable as limit switch, frequency output, pulse output or signal output for preset counter
IO-Link with block parameterization and data storage
Several sensor and process connection versions to fit different installations
Oil-filled version for high air humidity and heavily fluctuating temperatures
Specifications
INPUT |
|
Measuring principle | Calorimetric / thermal |
Measurement media | Liquids; media configurable on the device |
Measuring range, flow | 2...300 cm/s |
Measuring range, temperature | Corresponding to the specified media temperature range |
Signal input | Reset input for volume meter (alternative to switch output at Pin 5) |
MEASURING ACCURACY |
|
Measurement uncertainty, flow | ±(7 % measurement + 2 % FS) |
Measurement uncertainty, temperature | ±2 °C |
Condition | Flow speed > 2 cm/s |
Response time | Approx. 1-2 s in water (25 °C) at an average flow speed |
OUTPUTS |
|
Analog output, current | 4...20 mA; 0...20 mA |
Analog output, voltage | 0...10 V; 2...10 V; 0...5 V; 1...5 V; 0.5...4.5 V |
Switching outputs | 2 transistor outputs push-pull, parameterizable as NPN o.C.; short-circuit and reverse polarity resistant; Iout = 100 mA max per output |
Switching output functions | Configurable on the device as limit switch, frequency output, pulse output or signal output for preset counter |
IO-LINK |
|
IO-Link revision | V1.1 |
Bit rate | COM2 (38400 Bit/s) |
Minimum cycle time | 4 ms |
SIO mode | Yes |
Port class | A compatible |
Block parameterization | Yes |
Data storage | Yes |
DISPLAY |
|
Display | Graphic 1.2 inch LCD (transflective), 128 x 64 pixel |
Backlight | White, red on alarm notification |
Operation | Parameters programmable with multifunction ring |
POWER REQUIREMENT |
|
Supply voltage | 18...30 V DC |
Current consumption | < 130 mA (SIO mode, outputs not under load) |
ENVIRONMENTAL |
|
Media temperature, connection types 008 / 013 / 015 / 018 | -20...+90 °C |
Media temperature, connection type 012 | -20...+100 °C |
Operating pressure, connection types 008 / 015 | PN100 (PN200 on request) |
Operating pressure, connection types 013 / 018 | Up to PN100 (depending on T-piece) |
Operating pressure, connection type 012 | Up to PN40 (depending on assembly material) |
Ambient temperature | -20...+70 °C |
Storage temperature | -30...+80 °C |
Protection class | IP65 / IP67 |
MATERIALS |
|
Wetted materials | Stainless steel 1.4571; fluororubber (O-ring for connection type 013) |
Housing | Stainless steel 1.4305 |
Glass | Mineral glass, hardened |
Magnet | NeFeB |
Ring | POM |
MECHANICAL |
|
Electrical connection | M12x1 circular connector, 5-pin |
Pin assignment | 1 BN: L+; 2 WH: Analog; 3 BU: L-; 4 BK: IO-Link/DO; 5 GY: DI/DO |
Housing diameter | Ø50 mm |
Weight | Approx. 0.30 kg |
Sensor 012VK100 / 012VK150 | Push-in sensor Ø12, L = 100 mm / L = 150 mm (other lengths on request) |
Sensor 008HK028 | Thread G ¼ A, L = 28.0 mm |
Sensor 015HK029 | Thread G ½ A, L = 29.6 mm |
Sensor 015HK045 | Thread G ½ A, L = 45.0 mm |
Sensor 013TK031 | System fastening Ø13.2, L = 31 mm, for T-piece with connection G 3/8 and G ½ |
Sensor 013TK037 | System fastening Ø13.2, L = 37 mm, for T-piece with connection G ¾...G 2 |
Sensor 018DK045 | Sealing cone 24°, M18 x 1.5, L = 45 mm |
Oil-filled version (code T) | For applications with high air humidity and heavily fluctuating temperatures |
APPROVALS |
|
Conformity | CE |
Drawing

Downloads
| Senseca-OMNIPLUS-F-Datasheet-EN | DownloadSenseca-OMNIPLUS-F-Datasheet-EN |
|---|
Related Products

Senseca
OMNIPLUS-RRI-025 Impeller Flow Transmitter DN 25
Impeller flow transmitter for water and low-viscosity liquids, covering 2.100 l/min in DN 25 and PN 16, with LCD, IO-Link, analog output and two configurable…
Learn More
Senseca
SIMPLE R1 Adjustable Float Level Switch
Adjustable level switch for liquid monitoring in industrial and civil environments, with SPST or SPDT sealed contact, 500 or 1000 mm rod length, DIN 43650…
Learn More
Senseca
MULTIPOINT S Multi-Point Level Switch
Stainless steel (AISI 316) float level switch for liquid level control with up to 6 switch points, rod lengths up to 6 m, working pressure up to 50 bar and…
Learn More
Senseca
NW1 Float Level Switch for Side Installation
Float level switch for fluid media monitoring with reed switch, G ¾ A or G 1 A thread, normally open or normally closed contact, max.