WETEC

Senseca

PS4SK Pressure Switch for Industrial Process Monitoring

WaterProcess & Automation

Electronic pressure switch with ceramic diaphragm for absolute or relative pressure monitoring in gases, vapors, liquids and dust.

  • Measuring spans from 250 mbar to 600 bar

  • Characteristic deviation ≤ ±0.5% FS

  • 2 × PNP or 4…20 mA with 1 or 2 PNP switching outputs

  • Rotatable housing and LED display with 3-key operation

  • Stainless steel housing with IP65/IP67 protection

  • Process temperature −40…+100 °C, optionally extended to −40…+135 °C with temperature decoupler

Quantity
1

Overview

The Senseca Precont® PS4SK is an electronic pressure switch designed for monitoring absolute or relative pressure in gases, vapors, liquids and dust. It uses an aluminium oxide (Al₂O₃) ceramic diaphragm with thick-film strain gauge technology, offering measuring spans from 250 mbar to 600 bar and a characteristic deviation of ≤ ±0.5% FS. It is available with front-flush or internal diaphragm configurations and various stainless steel process connections.

The instrument features integrated evaluation electronics, a high-brightness LED display, function indicator LEDs and a three-key operating interface. Both the housing and display are rotatable to facilitate operation in different installation positions. Available output configurations include two PNP switching outputs or a 4…20 mA analogue output combined with one or two PNP switching outputs. The device operates on a 10.5…35 Vdc power supply, provides IP65/IP67 protection and supports process temperatures from −40 to +100 °C, with an optional extended range of −40 to +135 °C using a temperature decoupler.

Typical Applications

  • Pressure monitoring in machinery and plant engineering

  • Pressure measurement in air-conditioning and refrigeration systems

  • Pressure monitoring and control in hydraulic and pneumatic systems

  • Process pressure monitoring in the process industry

  • Pressure measurement in environmental technology systems

  • Pressure monitoring in facility and building automation systems

Key Features

  • Absolute or relative pressure measurement with measuring spans from 250 mbar to 600 bar, depending on configuration

  • Aluminium oxide (96% Al₂O₃) ceramic diaphragm with thick-film strain gauge technology

  • Characteristic deviation of ≤ ±0.5% FS

  • Long-term drift of ≤ ±0.2% FS per year (non-cumulative)

  • Front-flush or internal diaphragm configurations

  • Various stainless steel process connection options

  • Two PNP switching outputs or 4…20 mA analogue output with one or two PNP switching outputs

  • Rotatable housing and high-brightness LED display

  • Three-key operation with tactile feedback and function indicator LEDs

  • Standard process temperature range of −40…+100 °C, optionally extended to −40…+135 °C with a temperature decoupler

  • Ambient temperature range of −40…+85 °C

  • 10.5…35 Vdc power supply with reverse polarity protection

  • M12 × 1 electrical connector

  • IP65/IP67 protection

Benefits

  • Wide selection of measuring ranges to suit different pressure monitoring requirements

  • Accurate and stable measurements over long-term operation

  • Flexible installation with various industrial process connection options

  • Easy integration into control and monitoring systems through multiple output configurations

  • Clear display readability in different installation positions

  • Convenient local configuration without additional operating tools

  • Reliable operation under demanding environmental and process conditions within specified limits

  • Optional factory calibration and customer-specific preset configurations

Specifications

Pressure Measurement

Measuring principle

Thick-film strain gauge

Pressure type

Relative (gauge) or absolute pressure

Measuring media

Gases, vapors, liquids and dust

Measuring spans

250 mbar to 600 bar

Relative pressure range options

0…250 mbar, 0…400 mbar, 0…600 mbar, 0…1 bar, 0…1.6 bar, 0…2.5 bar, 0…4 bar, 0…6 bar, 0…10 bar, 0…16 bar, 0…25 bar, 0…40 bar, 0…60 bar, 0…100 bar, 0…160 bar, 0…250 bar, 0…320 bar, 0…400 bar, 0…600 bar, −1…0 bar, −1…+1 bar

Absolute pressure range options

Measuring ranges from 1 bar to 40 bar

Special measuring ranges

Optional

Diaphragm configuration

Front-flush or internal diaphragm

 

 

Measurement Accuracy

Characteristic deviation

≤ ±0.5% FS

Long-term zero-point drift

≤ ±0.2% FS/year (non-cumulative)

Temperature deviation

≤ ±0.05% FSI/K

Resolution

≥ 16 bit

Hysteresis

≤ ±0.1% FSI

Repeatability

≤ ±0.1% FSI

Supply voltage influence

≤ ±0.002% FSI/V

Mounting position influence

≤ 0.2 mbar (vertical position, sensor upwards)

 

 

Power Supply

Supply voltage

10.5…35 Vdc

Supply current

≤ 60 mA (analogue output max. 22.5 mA, switching output without load)

Reverse polarity protection

Provided

Start-up time

≤ 1 s

 

 

Switching Outputs

Switching function

PNP switching to +L

Output current

0…200 mA maximum

Output protection

Current limitation and short-circuit protection

 

 

Analogue Output

Nominal output signal

4…20 mA

Operating range

3.9…21 mA

Minimum output current

3.8 mA

Maximum output current

22 mA

Permitted load

≤ (Uₛ − 10.5 V)/22 mA

 

 

Electrical Connection and Output Configurations

Output configuration A

4-wire, 2 × PNP switching outputs

Output configuration B

4-wire, 1 × PNP switching output and 1 × 4…20 mA analogue output

Output configuration C

5-wire, 2 × PNP switching outputs and 1 × 4…20 mA analogue output

Output configuration D

4-wire, 1 × PNP switching output and 1 × 4…20 mA analogue output, DESINA

Electrical connector

M12 × 1 plug

 

 

Display and Operation

Display

High-brightness digital LED display

Status indication

Function indicator LEDs

Operating interface

Three-key operation with tactile feedback

Orientation adjustment

Rotatable housing and display

Evaluation electronics

Integrated

 

 

Materials

Diaphragm (process wetted)

Aluminium oxide ceramic (96% Al₂O₃)

Process connection (process wetted)

Stainless steel 1.4404/316L or 1.4571/316Ti

Terminal enclosure

CrNi steel

Gaskets (process wetted)

FPM fluoroelastomer (e.g. Viton®) or FDA-listed EPDM

 

 

Process Connections

Manometer thread

ISO 228-1 – G¼″ A or G½″ A, EN 837

Thread with sealing form E

ISO 228-1 – G¼″ A, DIN EN ISO 1179-2 E

Inner thread

ISO 228-1 – G¼″ I

Inner bore

ISO 228-1 – G½″

Front-flush connection

ISO 228-1 – G¾″ A, ≤ 10 bar

Front-flush connection

ISO 228-1 – G1″ A, ≤ 1 bar

ANSI NPT thread

NPT ¼″ or NPT ½″

 

 

Environmental and Process Conditions

Ambient temperature

−40…+85 °C

Standard process temperature

−40…+100 °C

Extended process temperature

−40…+135 °C, with temperature decoupler

Process pressure

0…600 bar, depending on process connection

Protection rating

IP65/IP67 according to EN/IEC 60529

 

 

Optional Configurations and Certifications

LABS-free/silicone-free version

Optional

Factory calibration

Available with calibration certificate

Customer-specific configuration

Optional preset configuration

Material test certificate

Optional, EN 10204 3.1

Drinking water suitability

Optional factory certification

Food suitability

Optional factory certification

Customer-specific marking

Measurement point designation (TAG), customer label or neutral type label

Drawing

PS4SK Pressure Switch for Industrial Process Monitoring Drawing

Downloads

PS4SK Datasheet DownloadPS4SK Datasheet
PS4SK Family User Manual DownloadPS4SK Family User Manual
PS4SK Family CE Declaration of Conformity DownloadPS4SK Family CE Declaration of Conformity