Senseca
PUKK Conductive Leakage Sensor
Floor-mounted conductive leakage sensor with integrated electronics.
Detects electrically conductive liquids from 5 µS/cm
PNP output (24 Vdc) or relay output (20…30 Vac/dc)
Adjustable sensitivity, IP68, floor mounting with screws
Overview
The PUKK is a compact floor probe for detecting leaks of electrically conductive liquids in places such as drip trays, raised floors, suspended ceilings and computer rooms with cooling channels. Its evaluation electronics are integrated in the sensor head, and it offers high protection against major water damage and system failures.
An alternating voltage is applied between the electrode contacts, which avoids electrode corrosion. When liquid bridges the electrodes, a measurable current flows and the electronics switch either a PNP output (24 Vdc version) or a relay output (20…30 Vac/dc version). Sensitivity can be adjusted to the conductivity of the liquid, and a yellow internal LED shows the switching state. It mounts on the floor with screws and comes with POM, PP or PTFE housings and 316L/316Ti or Hastelloy C4 electrodes.
Typical applications
Drip trays and bunds
Raised floors
Suspended ceilings
Computer rooms with cooling channels
Leakage monitoring of electrically conductive liquids
Key Features
Conductive leakage detection for liquids from 5 µS/cm
Evaluation electronics integrated in the sensor head
Alternating measuring voltage avoids electrode corrosion
1x PNP switching output (24 Vdc) or 1x relay output (20…30 Vac/dc)
Adjustable sensitivity to match liquid conductivity
Yellow internal LED shows switching state
Floor mounting with screw fixing
POM, PP or PTFE housing; 316L/316Ti or Hastelloy C4 electrodes
Terminal box or 5 m cable connection
IP68 protection, -20…+60 °C
Benefits
Early warning against major water damage and system failures
Compact design with evaluation electronics in the sensor head
Corrosion-resistant design
Easy installation on the floor
Material options for aggressive liquids
Specifications
MEASUREMENT |
|
Sensor type | Conductive |
Measuring range | ≥ 5 µS/cm / ≤ 200 kOhm |
Measuring voltage | ±9 Vpp ±1 V / 90 Hz / ≤ 1.5 mA (alternating voltage) |
Model | 2 electrodes, 1x limit |
Sensitivity | Adjustable to the conductivity of the liquid |
Status display | Yellow LED inside the device |
POWER SUPPLY |
|
Version G (DC) | 24 Vdc ±10%, reverse polarity protected, residual ripple ≤ 2 Vpp; power consumption ≤ 1 W; isolation voltage 1 kVac |
Version U (AC/DC) | 20…30 Vac/dc, 48…62 Hz, reverse polarity protected; power consumption ≤ 1.75 VA / 1 W; isolation voltage 2.5 kVac |
OUTPUTS |
|
Output A: PNP switching output (supply G only) | PNP, switching to +L/-L; Uo ≤ 0.2 V…≥ (Us - 2 V); Io = 0…500 mA (current limited ≤ 500 mA, short circuit proof); leakage current ≤ 100 µA; ≥ 100,000,000 switching cycles |
Output B: relay output (supply U only) | Potential-free changeover contact; ≤ 30 Vac/dc, 2 A, 62.5 VA / 60 W; ≥ 100,000 switching cycles (Pmax/Imax) |
Standby time / step response time | ton ≤ 1 s / t90 ≤ 2 s |
PROCESS CONDITIONS |
|
Process temperature | -20…+60 °C |
Process pressure | Pressureless |
ENVIRONMENTAL |
|
Ambient temperature | -20…+60 °C |
Storage and transport temperature | -20…+85 °C |
Protection degree | IP68 (EN/IEC 60529) |
Climatic classification | 4K4H (EN/IEC 60721-3-4) |
Shock / vibration | 15 g [11 ms] (EN/IEC 60068-2-27) / 4 g [10…2000 Hz] (EN/IEC 60068-2-6) |
EM compatibility | Operation device class B / industrial range (EN/IEC 61326) |
MATERIALS |
|
Electrodes (wetted) | Steel 1.4404/316L or 1.4571/316Ti; Hastelloy C4 |
Housing (wetted) | POM, PP or PTFE |
Seals (wetted) | NBR (POM/PP housing); FFKM (PTFE housing) |
MECHANICAL |
|
Dimensions | Ø 70 mm x 87 mm (height) |
Mounting | Floor mounting with screw fixing |
Electrical connection | Terminal box or 5 m cable |
Weight | 0.25 kg |
ORDER CODE |
|
Structure | PUKK - 2 (2 electrodes, 1x limit) - A (screw fixing) - electrode material - housing material - output - supply - electrical connection |
Electrode material | A: CrNi steel 316L/316Ti; D: Hastelloy C4 |
Housing material | D: POM; P: PP; T: PTFE |
Output / supply | A: 1x PNP switch output with G: 24 Vdc; B: 1x relay output with U: 20…30 Vac/dc |
Electrical connection | K: terminal box; V: cable 5 m |
Drawing

Downloads
| PUKK-Datasheet-EN | DownloadPUKK-Datasheet-EN |
|---|---|
| PUKK-Operating-Manual-EN | DownloadPUKK-Operating-Manual-EN |
Related Products

Senseca
SCM-300 Vibrating Fork Level Switch
Vibrating fork level switch for liquid limit detection in tanks, vessels and pipes, with DC-PNP or AC/DC output, pressure up to 40 bar and a WHG version…
Learn More
Senseca
USP4 Ultrasonic Level Transmitter
Ultrasonic level transmitter for non-contact level, volume and open-channel flow measurement in liquids, pastes and coarse bulk solids, with ranges up to 8 m.
Learn More
Senseca
USN Ultrasonic Level Transmitter
Non-contact ultrasonic level transmitter and switch for liquids, pastes and coarse bulk materials.
Learn More
Senseca
RP4SR Radar Level Sensor for Liquids
Non-contact 122 GHz FMCW radar level sensor for liquids in tanks up to 10 m. ≤ ±0.1% FSI, 10° beam, IO-Link with 0/4…20 mA or RS485 Modbus-RTU, IP65/IP67.
Learn More