WETEC

Senseca

RP4SR Radar Level Sensor for Liquids


Compact 122 GHz radar sensor for non-contact level measurement in liquids.

  • Measuring range 0…10 m, ≤ ±0.1% FSI, resolution ≤ 1 mm

  • IO-Link with 0/4…20 mA and 2 switching outputs, or RS485 Modbus-RTU

  • 10° beam angle, IP65/IP67, optional temperature measurement

Quantity
1

Overview

The Radarcont RP4SR is an electronic radar sensor for non-contact measurement of distance, level and volume in liquid media, in tanks up to 10 m. It uses a pulsed 122…123 GHz FMCW radar and measures the distance to the liquid surface from the change in delay and frequency of the reflected signal. Its narrow 10° beam angle reduces interference from foreign objects and tank internals.

It is a good choice where optical or ultrasonic sensors are unsuitable because of temperature, gas or vapour layers, over- or underpressure, dust, wind or incident light, and it can measure liquids with gas stratification or foam, or through the container wall (e.g. IPC containers) or a PTFE/PP protective window. Output is IO-Link with 0/4…20 mA and two push-pull switching outputs, or RS485 Modbus-RTU, both with integrated overvoltage protection. The slim M30x1.5 housing is rated IP65/IP67, with optional integrated temperature measurement.

Typical applications

  • Non-contact level and volume measurement of liquids

  • Storage tanks up to 10 m

  • Flow measurement at open channels and measuring weirs

  • Water and waste water sector

  • Process industry

  • Environmental technology

  • Applications where optical or ultrasonic sensors are unsuitable

Key Features

  • 122…123 GHz FMCW radar, non-contact measurement

  • Measuring range 0…10 m, blind zone ≤ 30 cm

  • Narrow 10° beam angle

  • Characteristic deviation ≤ ±0.1% FSI, resolution ≤ 1 mm

  • IO-Link with 0/4…20 mA and 2 switching outputs, or RS485 Modbus-RTU

  • Optional integrated temperature measurement

  • Integrated overvoltage protection

  • IP65/IP67, slim M30x1.5 housing

  • Support cable with steel core, up to 300 m

Benefits

  • Non-contact measurement, with no contact with the medium

  • Works where optical or ultrasonic sensors struggle: gas or vapour layers, foam, dust, wind, light or vacuum

  • Narrow beam reduces interference from tank internals

  • Can measure through the container wall (e.g. IPC containers) or through PTFE/PP protective windows

  • Easy integration via IO-Link, analog or Modbus

Specifications

DISTANCE INPUT

 

Sensor type

FMCW radar, pulsed

Frequency

122…123 GHz

Radiated power (EIRP)

≤ 10 dBm

Beam angle

10°

Pulse rate

≥ 10 Hz / ≤ 100 ms

Measuring range

0…10 m (FSI)

Blind zone

≤ 30 cm

Resolution

≤ 1 mm

Characteristic deviation

≤ ±0.1% FSI (linearity + repeatability + hysteresis)

Linearity

≤ ±0.1% FSI

Repeatability

≤ ±2 mm

Hysteresis

Negligible

Effect of auxiliary power

≤ ±0.002% FSI/V

Temperature effect

≤ ±0.005% FSI/K

Long-term drift

≤ ±0.02% FSI/year

Effect of mounting orientation

None

 

 

OUTPUTS

 

IO-Link version

IO-Link V1.1 / Port Class A / COM2 (38.4 kBaud), COM3 (230.4 kBaud); cycle time ≥ 2.3 ms; t90 ≤ 100 ms

Switching outputs (IO-Link version)

2x PP (push-pull), switching to +L/-L; Io = 0…200 mA (current-limited ≤ 450 mA, short-circuit proof); switching delay ≤ 30 µs; ≥ 100,000,000 switching cycles

Analog output (IO-Link version)

4…20 mA (3.8…20.5 mA, error ≤ 3.6 mA / ≥ 21 mA) or 0…20 mA (0…20.5 mA, error ≤ 0.05 mA / ≥ 21 mA); resolution ≤ 1 µA; load RL ≤ (Us - 8 V) / 22 mA

RS485 version

RS485 bidirectional, Modbus-RTU, 9600 baud (4800…38400 baud)

Surge protection

Integrated (EN/IEC 61000-4-5), insulation voltage ≥ 50 Vdc, rated discharge current 10 kA (8/20 µs)

 

 

TEMPERATURE (OPTIONAL)

 

Measuring range

-20…+70 °C (-4…+158 °F)

 

 

POWER REQUIREMENT

 

IO-Link version

9…35 Vdc (IO-Link inactive) / 18…30 Vdc (IO-Link active), reverse-polarity protected, residual ripple ≤ 2 Vpp; ≤ 20 mA

RS485 version

6…35 Vdc, reverse-polarity protected, residual ripple ≤ 2 Vpp

Switch-on delay

≤ 0.5 s

 

 

ENVIRONMENTAL

 

Process temperature

-20…+70 °C (-4…+158 °F)

Process pressure

-0.2…+0.5 bar

Ambient temperature

-20…+70 °C (-4…+158 °F)

Storage / transport temperature

-20…+85 °C

Protection degree

IP65/IP67 (EN/IEC 60529)

Climate class

4K4H (EN/IEC 60721-3-4)

Shock / vibration resistance

50 g [1 ms] (EN/IEC 60068-2-27) / 20 g [10…2000 Hz] (EN/IEC 60068-2-6)

EMC

Class B equipment / industrial environment (EN/IEC 61326)

Protection class / pollution degree

III / 4

Operating altitude

2000 m above sea level

 

 

MATERIALS

 

Not in contact with the process

PE-HD, POM, PA, FKM/FPM, PE, PUR, epoxy

Support cable

Steel core; breaking strength of steel shield ≥ 920 N; bending radius ≥ 100 mm; length L1 up to 300,000 mm

 

 

MECHANICAL

 

Process connection

Thread DIN 13 – M30x1.5

Housing length

140 mm

Weight

0.2 kg + 0.068 kg/m cable

Drawing

RP4SR-Dimensional-Drawing

Downloads

Radarcont-RP4SR-Datasheet-EN DownloadRadarcont-RP4SR-Datasheet-EN