WETEC

Senseca

USP4 Ultrasonic Level Transmitter


Non-contact ultrasonic level measurement up to 8 m

  • Measures level, volume and open-channel flow in liquids, pastes and coarse bulk solids without contact, with ranges up to 8 m.

  • 4…20 mA 2-wire output with a characteristic deviation of ≤ ±2 mm or ±0.2 % FSO and integrated overvoltage protection.

  • Set up via Bluetooth 5.0 LE, with an M12 plug version (IP65/IP67) or a cable version (IP68).

Quantity
1

Overview

The Senseca USP4 is an electronic ultrasonic level transmitter for monitoring, control and continuous measurement of filling levels in liquids, pastes and coarse bulk materials. It measures without contact at ranges up to 8 m and provides a 4…20 mA signal in 2-wire technology.

The device can be adjusted digitally via Bluetooth 5.0 LE, so it can be adapted to a wide variety of applications. It is available with an M12 connector plug or with an extension cable, and has integrated overvoltage protection, temperature compensation and interference echo suppression.

Typical applications

  • Non-contact level and volume measurement

  • Flow measurement at open channels and measuring weirs

  • Water and waste water sector

  • Process industry

  • Environmental technology

  • Storage tanks, storage bunkers, silos

Key Features

  • Measuring ranges up to 8 m (0…2 m, 0…5 m or 0…8 m)

  • Non-contact measurement in liquids, pastes and coarse bulk materials

  • Electronic 4…20 mA in 2-wire technology

  • High accuracy: characteristic deviation ≤ ±2 mm or ±0.2 % FSO

  • Operating interface Bluetooth® 5.0 LE with envelope curve indication

  • Temperature compensation and interference echo suppression

  • Integrated overvoltage protection

  • M12 connector plug or extension cable version

  • Protection class IP65 / IP67 (plug) or IP68 (cable)

  • Process temperature range –20 °C to +70 °C

Benefits

  • Non-contact measurement of liquids, pastes and coarse bulk materials

  • Digital adjustment via Bluetooth 5.0 LE adapts the device to a wide variety of applications

  • Interference echo suppression and envelope curve indication are available through the Bluetooth interface

  • Shock classification 50 g and vibration classification 20 g, with IP68 protection on the cable version

  • Maintenance-free device; the diaphragm should be cleaned regularly if solid coatings form

  • Optional LABS-free / silicone-free version, laser-marked TAG or customer label, and customer-specific preset configuration

Specifications

INPUT

 

Measuring range

MB-02: 0…≤ 2 m; MB-05: 0…≤ 5 m; MB-08: 0…≤ 8 m

Blocking distance BD

MB-02: ≤ 0.10 m (typ. 0.06 m); MB-05: ≤ 0.15 m (typ. 0.10 m); MB-08: ≤ 0.30 m (typ. 0.19 m)

Operating frequency

MB-02: 125 kHz; MB-05: 75 kHz; MB-08: 50 kHz

Emitting angle α (-3 dB)

MB-02: 10° ±2°; MB-05: 14° ±2°

Detection radius rx = tan (α / 2) × Lx

MB-02: 0.087 m (Lx = 1.0 m) / 0.175 m (Lx = 2.0 m); MB-05: 0.307 m (Lx = 2.5 m) / 0.614 m (Lx = 5.0 m)

Pulse rate tp (measuring cycle time)

MB-02: ≤ 10 Hz / ≥ 100 ms; MB-05: ≤ 4 Hz / ≥ 250 ms; MB-08: ≤ 2 Hz / ≥ 500 ms

 

 

MEASURING ACCURACY

 

Reference conditions

EN/IEC 60770-1, limit value adjustment: 15…25 °C / 860…1060 kPa / 45…75 % r.H. / ton 240 s / 24 VDC ±0.1 V / vertical, process connection bottom, ideal reflective surface, no interference reflections within signal beam

Characteristic deviation

≤ ±2 mm or ±0.2 % FSO (nonlinearity + hysteresis + reproducibility; FSO = nominal measuring range)

Influence of auxiliary power

≤ ±0.002 % FSO/V

Long term drift

≤ ±0.2 % FSO/year

Temperature deviation

Tk zero (mean value) ≤ ±0.006 % FSO/K

 

 

OUTPUTS

 

Analogue output

4…20 mA, 2-wire: 3.8…20.5 mA / ≥ 3.6 mA / ≤ 22 mA / dI ≤ 1 µA

Current alarm (default)

Hold value 3.8…20.5 mA (selectable: hold value 3.8…20.5 mA / 3.6 mA / 22 mA)

Permitted load

RL ≤ (Us - 11 V) / 22 mA

Time behavior

T90 ≤ pulse rate tp (td = 0 s) / ton ≤ 3 s (td = 0 s)

Interface

Bluetooth 5.0 LE (2 Mbit/s)

Bluetooth transmit power

≤ 0.1 W

Bluetooth range

Outdoor max. 200 m / indoor max. 40 m

 

 

POWER REQUIREMENT

 

Supply voltage Us

11…35 VDC, polarity protected

Residual ripple voltage

≤ 2 Vpp

Supply current

≤ 22 mA

Overvoltage protection, coarse

Cable types K/H/0: 75 V / 10 kA, wave 8/20 µs, +L/-L to cable shield; plug type S: 150 V / 10 kA, wave 8/20 µs, +L to -L

Overvoltage protection, fine

36 V / all lines to -L

 

 

ENVIRONMENTAL

 

Process temperature

-20 °C…+70 °C

Process pressure

-0.3…2 bar (low pressure ≤ -0.2 bar influences the measuring result)

Environmental temperature

-20 °C…+70 °C

Protection level

Cable types K/H/0: IP68 [≤ 3 m / ≤ 0.3 bar]; plug type S: IP65 / IP67 (EN/IEC 60529)

Climatic classification

4K4H (EN/IEC 60721-3-4)

Shock classification

50 g [11 ms] (EN/IEC 60068-2-27)

Vibration classification

20 g [10…2000 Hz] (EN/IEC 60068-2-6)

EM compatibility

Operation device class B / industrial range (EN/IEC 61326)

MTTF

388 years

 

 

MATERIALS

 

Process wetted

PVDF, POM, PA, NBR, FPM, PE, PUR

 

 

MECHANICAL

 

Process connection

Thread M30x1.5

Electrical connection

Cable (types K, H, 0) or M12 plug (type S)

Tightening torque

≤ 20 Nm

Weight, cable types K/H/0

MB-02: 0.2 kg + (L1 × 0.068 kg/m); MB-05: 0.3 kg + (L1 × 0.068 kg/m)

Weight, plug type S

MB-02: 0.2 kg; MB-05: 0.3 kg

Cable breaking force

> 900 N

Cable bending radius

> 120 mm

Cable cross-section

0.22 mm²

Cable resistance

90 Ohm/km

 

 

APPROVALS

 

Conformity

CE mark (meets the requirements of all relevant EU directives)

Drawing

Senseca-USP4-Dimensional-Drawing

Downloads

Sonicont-USP4-Datasheet-EN DownloadSonicont-USP4-Datasheet-EN