Senseca
GHTU Humidity and Temperature Transducer
Humidity and temperature transducer for wall, duct and open-air use.
- Humidity 0.0…100.0 %RH and temperature -40.0…+120.0 °C
- 4…20 mA standard output (0…1 V or 0…10 V optional), with a 4-digit LCD alternating humidity and temperature
- ABS housing, IP65, with min/max memory and adjustable offset and slope
Overview
The GHTU is a humidity and temperature transducer built with the latest microprocessor technology. It measures 0.0…100.0 %RH (temperature compensated) and -40.0…+120.0 °C, and comes in wall, wall/duct, duct, cable and open-air versions. It has a 4-digit LCD and standard signal outputs, in an ABS housing (IP65).
Typical applications
Different versions let the GHTU be used in almost all applications.
- Wall mounting (GHTU-1R-MP, GHTU-1K-MP)
- Duct (channel) mounting (GHTU-1K-MP, GHTU-2K-MP)
- Open-air measurement with the heat absorption hat / weather protection shield (GHTU-SHUT-MP)
- Wall mounting with a separated sensor tube on a 1 m cable and high-humidity sensor (GHTU-KABEL-MP)
Key Features
Precise and flexible humidity and temperature measurement with a built-in display.
- Temperature compensated humidity measurement, with automatic temperature compensation
- 4…20 mA standard output; 0…1 V and 0…10 V options, including galvanically isolated versions
- 4-digit LCD display (approx. 10 mm high) alternating humidity and temperature
- Min/max value memory, offset and slope adjustable, output signal scaleable
- Optional UNI display: show wet bulb temperature, dew point temperature, enthalpy, atmospheric humidity or absolute humidity instead of the humidity value
- Optional high-humidity sensor; optional encapsulated PC board for use where condensation may occur
- Fitting lengths of 50, 220, 300, 400 or 500 mm
Benefits
- Flexible mounting: wall, duct, separated probe and weather shield versions support room, duct and open-air use
- Wide sensor range: measures 0.0…100.0 %RH and sensor temperatures from -40.0…+120.0 °C
- Process-ready output: 4-20 mA is standard; 0-1 V and 0-10 V options are available
- Protected housing: ABS housing and EN 175301-803/A elbow-type plug are rated IP65
- On-site adjustment: min/max memory, offset and slope adjustment, and scalable output support setup
Specifications
SPECIFICATIONS |
|
Humidity measuring range | 0.0…100.0 %RH (temperature compensated) |
Temperature measuring range | -40.0…+120.0 °C or -40.0…+248 °F |
Recommended humidity range | 20.0…80.0 %RH (standard) |
Display options (option UNI) | An alternative display unit can be shown instead of the humidity measuring value, selected via keyboard: |
Accuracy (at 25 °C and in recommended range) | Display, humidity: ±2.5 %RH |
Temperature compensation | Automatically |
Auxiliary energy | 12…30 VDC or 18…30 VDC (for output: 0-10 V) |
Reverse voltage protection | 50 V, permanently |
Permissible impedance (at 4-20 mA) | RA [Ω] ≤ (UV [V] - 12 V) / 0.02 A |
Permissible load (at 0-1(10) V) | RL [Ω] > 3000 Ω |
Display | Approx. 10 mm high, 4-digit LCD display, alternating humidity and temperature display |
Working temperature | Electronics: -25…+50 °C |
Storage temperature | -25…+70 °C |
Relative humidity (electronic) | 0…95 %RH (non-condensing). If there is a risk of condensation due to temperature changes, use the encapsulated or lacquered types (optionally available). |
DESIGN & MOUNTING |
|
Models | GHTU-1R-MP: wall version, standard probe length 50 mm (Product-ID 602585) |
Housing | ABS (IP65) |
Sensor tube | Tube 14 mm Ø, with screw-type protection cap |
Design type Kabel | With separated sensor tube, sensor head (Ø14 x 68 mm) connected to device via 1 m Teflon cable. Includes option high-humidity sensor. |
Design type Shut | Heat absorption hat / weather protection shield, especially designed for measurements in the open air. The measuring results are not influenced by either sun or rain. |
Electric connection | Elbow-type plug acc. to EN 175301-803/A (IP65) |
Mounting | 4 housing holes for wall mounting or by means of plastic tube clamps for duct mounting |
Functions | Min-/max-value memory, offset and slope adjustable, output signal scaleable |
ORDERING CODE | GHTU - 1 - 2 - 3 - 4 - 5 - 6 -GE |
1. Design type | 1R-MP = Surface design |
2. Fitting length EL | -050 = 50 mm (standard for 1R) |
3. Output signal | ... = 4-20 mA (standard) |
4. Options sensor | -00 = Standard sensor |
5. Option | -LACK = Encapsulated PC board |
6. Option | -UNI = Selectable humidity display instead of the standard humidity values |
Downloads
| GHTU Family Datasheet (EN) | DownloadGHTU Family Datasheet (EN) |
|---|
Related Products

Senseca
BTD-200 Lightning Warning System
Self-contained lightning warning system detecting cloud-to-ground, intra-cloud and cloud-to-cloud lightning up to 35 km, with early overhead warning, 3 relays…
Learn More
Senseca
BTD-1 Thunderstorm Warning System
Standalone thunderstorm warning system detecting lightning up to 35 km (83 km option) from the quasi-electrostatic field, with early warning, Severe Storm…
Learn More
Senseca
HD2021T6 - HD2021T7 Luminance Transmitters
Luminance transmitters for tunnel and road lighting control, converting cd/m² into 0…10 V or 4…20 mA, with ranges up to 200 kcd/m², IP52 and versions for Lv…
Learn More
Senseca
ALS-2 Ambient Light Sensor
Ambient light sensor for runway visual range (RVR) systems, measuring background luminance from 0 to 40,000 cd m-2, with RS232/RS422/RS485 outputs and heated…
Learn More