Senseca
UNICON-PH-01/02 pH and ORP Converter
pH and ORP converter for industrial process monitoring with head or field mounting.
Programmable range: −1.00…+15.00 pH or −1500…+1500 mV
Pt100/Pt1000 temperature compensation
4…20 mA pH/ORP output and two transistor alarm outputs
1- or 2-point pH calibration
IP65 housing with 2-line LCD display
Overview
The Senseca UNICON-pH is a pH and ORP converter designed for process measurements in food technology, chemical processing, pharmaceutical applications and wastewater treatment. It is compatible with common pH and ORP electrodes and supports head mounting directly on the electrode or field mounting with a separate connection cable. The programmable measuring range covers −1.00…+15.00 pH or −1500…+1500 mV, with selectable Pt100 or Pt1000 temperature compensation.
The converter provides a 4…20 mA pH/ORP output, two programmable transistor alarm outputs and 1- or 2-point pH calibration. Model 2 additionally supports a second measuring range, a 4…20 mA temperature output, glass and reference electrode impedance monitoring, and calibration interval monitoring. The instrument features a 2-line LCD display, a front-panel membrane keypad and an IP65 housing, powered by a 14…30 V DC supply.
Typical Applications
pH and ORP monitoring in food processing
Process measurements in chemical industries
pH and ORP monitoring in pharmaceutical processes
pH and ORP monitoring in wastewater treatment
Key Features
Compatible with common pH and ORP electrodes with a nominal electrode zero point of pH 7.00
Programmable measuring range of −1.00…+15.00 pH or −1500…+1500 mV
Selectable Pt100 or Pt1000 temperature compensation
Temperature measuring range of −40…+160 °C
4…20 mA analogue output for pH/ORP
Two programmable transistor alarm outputs
1- or 2-point pH calibration with selectable buffer sets
Head or field mounting configuration
2-line LCD display with front-panel membrane keypad
IP65 housing with IP20 screw terminals
Second measuring range switchable by an external control signal (Model 2)
Additional 4…20 mA temperature output (Model 2)
Glass and reference electrode impedance monitoring (Model 2)
Calibration interval monitoring from 1…1000 days (Model 2)
Benefits
Supports existing pH and ORP electrodes without requiring a dedicated electrode type
Flexible measuring range configuration to suit different process requirements
Temperature compensation helps maintain pH measurement accuracy
Easy integration into process monitoring and control systems
Flexible mounting to suit different installation layouts
Convenient local configuration and measurement viewing
Selectable calibration methods to suit electrode conditions
Supports planned electrode maintenance through impedance and calibration interval monitoring (Model 2)
Allows measuring range switching without manual reconfiguration (Model 2)
Specifications
Power Supply | |
|---|---|
Supply voltage | 14…30 V DC |
Supply configuration | 2-wire, loop-powered |
Isolation | pH/ORP output, temperature output, alarm outputs 1 and 2, and range switch input |
Test voltage | 500 V DC |
pH and ORP Measurement | |
|---|---|
pH measuring range | −1.00…+15.00 pH, programmable |
ORP measuring range | −1500…+1500 mV, programmable |
Input resistance | >10¹² Ω |
Input current | <10⁻¹² A |
Nominal electrode zero point | pH 7.00 |
Electrode zero point deviation | ±2.0 pH |
Electrode slope | 30…80 mV/pH |
ORP offset | ±200 mV |
Accuracy | 0.2% of measured value, ±2 digits (datasheet)* |
Temperature coefficient | <100 ppm/°C |
Measuring rate | Approx. 2 measurements/s |
Calibration | |
|---|---|
pH calibration | 1- or 2-point calibration |
Calibration modes | Automatic buffer identification, manual calibration and direct data entry |
Selectable buffer sets | WTW, Schott, Ingold (Mettler Toledo), DIN 19266 |
Manual buffer input | Supported |
Direct data entry | Electrode zero point and slope |
Automatic calibration requirement | Electrode with integrated temperature sensor |
Temperature Measurement and Compensation | |
|---|---|
Temperature sensor | Pt100 or Pt1000, software selectable |
Sensor connection | 2-wire |
Measuring range | −40.0…+160.0 °C (−40.0…+320.0 °F) |
Temperature unit | °C or °F, programmable |
Minimum measuring span | 25.0 °C (45.0 °F) |
Maximum measuring span | 200 °C (360 °F) |
Accuracy | ±0.1%, ±1 digit |
Temperature coefficient | <50 ppm/°C |
Linearisation error | ±0.1% |
Analogue Outputs | |
|---|---|
pH/ORP output signal | 4…20 mA |
Temperature output signal | 4…20 mA (Model 2 only) |
Load resistance | Rₐ ≤ (Uᵦ − 14 V) / 0.02 A |
Alarm Outputs | |
|---|---|
Number of outputs | 2 |
Output type | Transistor |
Voltage | 14…30 V DC |
Maximum current | 60 mA |
Voltage drop | <2 V |
Output protection | Short-circuit protection |
Switching function | Programmable minimum or maximum function |
Measuring Range Switching (Model 2 Only) | |
|---|---|
Switching method | External control signal |
Switching capability | Selection of second measuring range or switching between pH and ORP measurement |
Input resistance | >10 kΩ |
Measuring range 1 active | 0…3 V DC |
Measuring range 2 active | 12…30 V DC |
Electrode Monitoring (Model 2 Only) | |
|---|---|
Glass impedance | 0…1 GΩ, temperature compensated |
Glass impedance detection range | 0.001…2 GΩ, non-compensated |
Glass impedance accuracy | ±20% |
Reference impedance | 0…100 kΩ, non-compensated |
Reference impedance accuracy | ±20% |
Calibration interval monitoring | 1…1000 days |
Display and Operation | |
|---|---|
Display type | Dot-matrix LCD |
Display format | 2 lines, 16 characters per line |
Character height | 3.8 mm |
Operation | Front-panel membrane keypad |
Front keypad material | Polyester |
Housing and Mechanical | |
|---|---|
Mounting configuration | Head mounting or field mounting |
Housing material | Polyamide PA6-GF/GK 15/15 |
Housing dimensions (W × H × D) | 100 × 100 × 60 mm |
Weight | Max. 360 g |
Housing protection | IP65 |
Terminal protection | IP20 |
Electrical connection | Screw terminals with pressure plate |
Flexible wire cross-section | 2.5 mm² |
Single-wire cross-section | 4 mm² |
Cable glands (dimensional drawing) | 2 × M20 × 1.5 |
Cable diameter | 6…12 mm |
Environmental Conditions | |
|---|---|
Operating temperature | 0…+50 °C (32…122 °F) |
Standards and Conformity | |
|---|---|
EMC directive | 2014/30/EU |
RoHS directive | 2011/65/EU |
EMC standard | EN IEC 61326-1:2013 |
RoHS standard | EN IEC 63000:2018 |
Drawing
Downloads
| Unicon-Ph Family Datasheet | DownloadUnicon-Ph Family Datasheet |
|---|---|
| Unicon-Ph Family User Manual | DownloadUnicon-Ph Family User Manual |
| Unicon-Ph-De-En-2086 Family CE Declaration of Conformity | DownloadUnicon-Ph-De-En-2086 Family CE Declaration of Conformity |
Related Products
Senseca
UNICON-LF-01/02/03 Conductivity Converter
Conductivity converter for liquid purity and concentration monitoring.
Learn More
Senseca
LF4003 Conductivity Cell for Wells and Open Water Systems
4-electrode immersion conductivity cell for wells and open systems up to 100 m depth.
Learn More
Senseca
ORP211 Combined Redox Electrode for Polluted Wastewater Media
Combined Redox electrode for heavily polluted media in wastewater and process chemistry.
Learn More
Senseca
CONDIX4213 Digital Conductivity Transmitter
Digital conductivity converter for water treatment and industrial liquid monitoring.
Learn More