DLF4 Data Logger for Autonomous Sensor Data Transmission

WaterProcess & Automation

Autonomous multi-channel data logger and sensor gateway for long-term measurement recording.

  • Supports up to 7 sensors with analog, RS485 Modbus RTU and digital inputs

  • Optional mobile data transmission to the ACS Web Portal or FTP server

  • Bluetooth 5.2 configuration

  • Non-volatile memory for ≥800,000 measured values

  • Battery, rechargeable battery and DC supply options, with PV charging for the rechargeable battery

  • Flood and low-water alarm management

  • IP68 housing, submersible up to 3 m

Quantity
1

Overview

The Senseca DLF4 is an autonomous multi-channel data logger and sensor gateway designed for long-term measurement recording and remote monitoring. It supports up to 7 connected sensors with analog inputs of 0/4…20 mA, 0…10 V and 0…2200 Ω, RS485 Modbus RTU communication, and digital switch or pulse counter inputs. Measurements are stored in non-volatile Dataflash memory with a capacity of ≥800,000 measured values, with optional mobile data transmission to the ACS Web Portal or an FTP server.

The device supports local configuration via Bluetooth 5.2 and remote configuration through the web portal when mobile communication is enabled. Power supply options include 19 Ah or 35 Ah lithium batteries, a 20 Ah rechargeable lithium-ion battery and an external 7…32 Vdc supply, with PV charging available for the rechargeable battery. Its hermetically sealed IP68 housing is submersible up to 3 m, while integrated alarm management enables early detection and reporting of flooding or low-water conditions.

Typical Applications

  • Long-term multi-sensor monitoring at remote and unattended measuring sites

  • Water level monitoring for flood and low-water detection

  • Flow monitoring using pulse-output flow meters

  • Autonomous outdoor monitoring where external power supplies are unavailable

Key Features

  • Multi-channel data acquisition for up to 7 connected sensors

  • Analog inputs of 0/4…20 mA, 0…10 V and 0…2200 Ω

  • Two internally interconnected RS485 Modbus RTU inputs with alternating operation

  • Two configurable digital switch or pulse counter inputs

  • Integrated sensor power supply outputs

  • Optional automatic data transmission to the ACS Web Portal or FTP server via LTE-M1, LTE-NB2 or EGPRS

  • Bluetooth 5.2 interface for local configuration

  • Non-volatile Dataflash memory for ≥800,000 measured values

  • 19 Ah or 35 Ah lithium battery, 20 Ah rechargeable lithium-ion battery and 7…32 Vdc supply options, with PV charging for the rechargeable battery

  • Integrated flood and low-water alarm management

  • Hermetically sealed IP68 aluminum housing, submersible up to 3 m

  • Wall or mast mounting, with an optional bracket for 50…90 mm mast diameters

Benefits

  • Flexible integration of multiple sensors with different signal types into a single data logger

  • Reduced need for site visits through optional automatic remote data transmission

  • Convenient on-site wireless configuration without opening the housing

  • Long-term retention of recorded measurements in non-volatile memory

  • Autonomous operation at locations without a permanent power supply

  • Early notification of flooding or low-water conditions

  • Protection against water ingress in demanding outdoor environments

  • Flexible installation on walls or masts

Specifications

Auxiliary Power Supply

Battery B1

Lithium, 3.6 V / 19 Ah

Battery B2

Lithium, 3.6 V / 35 Ah

Rechargeable battery A1

Li-ion, 4.1 V / 20 Ah

DC voltage

7…32 Vdc / ≤350 mA

PV module

4.5…32 Vdc / ≤2 A

 

 

Analog – Current

Input channels

Ai1 / Ai2

Signal range

0/4…20 mA

Full-scale input (FSI)

0…28 mA

Input resistance (Ri)

27 Ω

Resolution

16 bits FSI

Characteristic curve deviation

≤±0.05% FSI

Temperature deviation

≤±0.1% FSI / 10 K

Long-term drift

≤±0.05% FSI/year

 

 

Analog – Voltage

Input channels

Ai1 / Ai2

Signal range

0…10 V

Full scale (F.S.)

0…19 V

Input resistance (Ri)

1.2 MΩ

Resolution

16 bits FSI

Characteristic curve deviation

≤±0.05% FSI

Temperature deviation

≤±0.1% FSI / 10 K

Long-term drift

≤±0.05% FSI/year

 

 

Analog – Resistance

Input channel

Ai3

Signal range

0…2200 Ω

Full-scale input (FSI)

0…2200 Ω

Output current (Io)

340 µA

Resolution

16 bits FSI

Characteristic curve deviation

≤±0.05% FSI

Temperature deviation

≤±0.1% FSI / 10 K

Long-term drift

≤±0.05% FSI/year

 

 

Communication – RS485 Modbus RTU

Communication channels

Ci1 / Ci2

Interface

Bidirectional RS485

Communication protocol

Modbus RTU

Baud rate

9600 baud (4800…38400 baud)

Input resistance

96 kΩ

Channel operation

Internally interconnected, operating alternately when two sensors are connected

 

 

Digital – Switch / Counter

Input channels

Di1 / Di2

Input function

Switch / counter

Operating resistance

≤20 kΩ

Operating frequency

≤1 kHz

 

 

Transmitter Power Supply Voltage Uo1 / Uo2 – Standard Version

Output voltage at 0 mA

16.6 V ±0.3 V

Output voltage at 30 mA

15.9 V ±0.3 V

Output current range

0…30 mA

Maximum output current

40 mA

 

 

Transmitter Power Supply Voltage Uo1 / Uo2 – Ex Version

Output voltage at 0 mA

21.8 V ±0.3 V

Output voltage at 30 mA

11.8 V ±0.3 V

Output current range

0…30 mA

Maximum output current

40 mA

Internal resistance (Ri)

≤306 Ω

 

 

Transmitter Power Supply Voltage Uo3 / Uo4

Output voltage at 0 mA

6.7 V ±0.2 V

Output voltage at 100 mA

6.6 V ±0.2 V

Output current range

0…100 mA

Maximum output current

300 mA

 

 

Transmitter Power Supply Voltage Uo5

Output voltage at 0 mA

3.8 V ±0.2 V

Output voltage at 100 mA

3.0 V ±0.2 V

Output current range

0…100 mA

Maximum output current

220 mA

 

 

Bluetooth Interface Outputs

Standard

Bluetooth® 5.2

Data transmission rate

2 Mbit/s

Advertising mode

2 s

Transmit power

≤0.1 W

Outdoor range

Max. 200 m

Indoor range

Max. 40 m

 

 

Mobile Communication Interface (Optional) Outputs

4G LTE-M1 bands (LTE-FDD)

B1/B2/B3/B4/B5/B8/B12/B13/B18/B19/B20/B25/B26/B27/B28/B66/B85

4G LTE-NB2 (NB-IoT) bands (LTE-FDD)

B1/B2/B3/B4/B5/B8/B12/B13/B18/B19/B20/B25/B28/B66/B71/B85

2G EGPRS frequency bands

850/900/1800/1900 MHz

Network priority

4G (LTE-M1 or LTE-NB2), fallback to 2G (EGPRS)

4G transmit power

≤0.2 W

2G transmit power

≤2 W

SIM

Internal SIM + external Micro-SIM

Antenna connector

SMA connector / 50 Ω

 

 

Data Logger Memory

Memory type

Non-volatile Dataflash

Memory capacity

8 MB

Storage capacity

≥800,000 measured values

 

 

Data Logger Time

Time accuracy with Internet time synchronization

≤±4 s/month, with synchronization once a day

Time accuracy without Internet time synchronization

≤±2 minutes/month

Frequency standard

Quartz

 

 

Environmental Conditions

Ambient temperature (Ta)

−20…+60 °C (−4…+140 °F)

Li-ion battery charging temperature [03-A1]

0…+45 °C (+32…+113 °F), internally limited

Protection class

IP68 (≤3 m / ≤0.3 bar), EN/IEC 60529

Climate class

4K4H (EN/IEC 60721-3-4)

Shock resistance

15 g (11 ms), EN/IEC 60068-2-27

Vibration resistance

4 g (10…2000 Hz), EN/IEC 60068-2-6

EMC

Class B equipment / industrial environment (EN/IEC 61326)

Operating altitude

2,000 m above sea level

Mean time to failure (MTTF)

258 years

Weight – Standard version [01-S]

1.2 kg

Weight – ATEX version [01-X5]

2.8 kg

 

 

Materials

Materials in contact with the process

Aluminum, PA, PUR, brass, nickel, silicone, NBR

 

 

Reference Conditions

Reference ambient temperature (Ta)

+15…+25 °C (+59…+77 °F)

Relative humidity

45…75%

Reference battery capacity

35 Ah

Reference time (ton)

240 s

Measurement deviation

EN/IEC 60770-1: Calibration curve deviation – Setpoint adjustment

Drawing

DLF4 Data Logger for Autonomous Sensor Data Transmission Drawing