WETEC

Senseca

HLF4 Autonomous Data Logger for Water Level Monitoring in 2" Pipes

WaterProcess & Automation

Autonomous data logger for water level monitoring in narrow pipes from 2".

  • 0/4…20 mA, RS485 Modbus RTU and switch/counter inputs

  • Bluetooth® configuration and optional 4G/2G remote data transmission

  • Non-volatile memory for at least 800,000 measured values

  • Alarm management for flooding and low water levels

  • IP68 housing, submersible up to 3 m

  • Lithium battery, rechargeable Li-ion battery and DC supply options, with PV charging for the Li-ion battery

Quantity
1

Overview

The Senseca Hydrolog® HLF4 is an autonomous data logger designed for water level monitoring in narrow pipes from 2". It records measured values from connected level probes, ultrasonic sensors, radar sensors and similar measuring devices. It supports 0/4…20 mA analogue inputs, RS485 Modbus RTU interfaces and a digital switch/counter input, with integrated temporary sensor power supply and non-volatile memory for at least 800,000 measured values.

The data logger supports Bluetooth® configuration and optional remote data transmission to a web portal or FTP server via LTE-M1, LTE-NB2 or EGPRS cellular networks. It features alarm management for flooding and low water levels, together with an IP68 housing that withstands submersion up to 3 m. Power supply options include lithium batteries, a rechargeable Li-ion battery and external DC supply, with photovoltaic charging available for the rechargeable battery configuration.

Typical Applications

  • Water level monitoring in water and wastewater systems

  • Environmental water level monitoring

  • Long-term water level monitoring at hydroelectric power plants

  • Flood and low water level alerting

  • Water level monitoring for weir control

  • Storage tank level monitoring and inventory management

  • Water level monitoring in industrial processes

Key Features

  • Compact Ø 48 mm housing for installation in water level pipes from 2"

  • Supports up to 5 connected sensors and 11 measured variables

  • Two 0/4…20 mA analogue inputs, two RS485 Modbus RTU interfaces and one digital switch/counter input

  • Four temporary sensor power supply outputs: two 16.6 V and two 6.7 V

  • Non-volatile Dataflash memory with 8 MB capacity for at least 800,000 measured values

  • Bluetooth® 5.2 interface for local configuration and operation

  • Optional remote data transmission to a web portal or FTP server via LTE-M1, LTE-NB2 or EGPRS

  • Alarm management for flooding and low water levels

  • IP68 housing, submersible up to 3 m

  • Ambient temperature range -20…+60 °C

  • 19 Ah or 35 Ah lithium battery, 20 Ah rechargeable Li-ion battery and 7…32 Vdc supply options

  • Photovoltaic charging support for the rechargeable Li-ion battery configuration

  • Quartz-based timekeeping with support for daily Internet time synchronization

Benefits

  • Compact design allows installation in narrow water level pipes

  • Flexible sensor compatibility simplifies integration with different monitoring systems

  • Integrated sensor power supply reduces the need for separate sensor power sources

  • Optional remote data transmission reduces the need for routine site visits

  • Wireless Bluetooth® configuration simplifies local operation

  • Non-volatile memory retains recorded measurement data during power interruptions

  • Alarm management enables timely reporting of flooding and low water levels

  • Submersible housing provides protection in flood-prone locations

  • Flexible power supply options accommodate different installation requirements

  • Energy-efficient design supports long-term autonomous monitoring

Specifications

Auxiliary Power Supply

Lithium battery (B1)

3.6 V, 19 Ah

Lithium battery (B2)

3.6 V, 35 Ah

Rechargeable Li-ion battery (A1)

4.1 V, 20 Ah

DC supply

7…32 Vdc / ≤350 mA

PV module (A1 configuration)

4.5…32 Vdc / ≤2 A

 

 

Analogue Inputs – Current

Input channels

Ai1 / Ai2

Signal range

0/4…20 mA

Full-scale input (FSI)

0…28 mA

Input resistance

27 Ω

Resolution

16 bits FSI

Characteristic curve deviation

≤±0.05% FSI

Temperature deviation

≤±0.1% FSI / 10 K

Long-term drift

≤±0.05% FSI/year

 

 

Communication Inputs – RS485 Modbus RTU

Interface channels

Ci1 / Ci2

Interface

RS485, bidirectional

Communication protocol

Modbus RTU

Baud rate

9600 baud (4800…38400 baud)

Input resistance

96 kΩ

 

 

Digital Input – Switch / Counter

Input channel

Di1

Input type

Switch / Counter

Operating resistance

≤20 kΩ

Operating frequency

≤1 kHz

 

 

Transmitter Power Supply

Supply function

Temporary sensor power supply

Output voltage (Uo1 / Uo2)

16.6 V ±0.3 V (0 mA); 15.9 V ±0.3 V (30 mA)

Output current (Uo1 / Uo2)

0…30 mA, max. 40 mA

Output voltage (Uo3 / Uo4)

6.7 V ±0.2 V (0 mA); 6.6 V ±0.2 V (100 mA)

Output current (Uo3 / Uo4)

0…100 mA, max. 300 mA

 

 

Bluetooth Interface

Standard

Bluetooth® 5.2

Data rate

2 Mbit/s

Advertising mode

2 s

Transmit power

≤0.1 W

Outdoor range

Max. 200 m

Indoor range

Max. 40 m

 

 

Cellular Communication Interface (Optional)

Communication standards

4G LTE-M1, 4G LTE-NB2 (NB-IoT), 2G EGPRS

LTE-M1 frequency bands (LTE-FDD)

B1/B2/B3/B4/B5/B8/B12/B13/B18/B19/B20/B25/B26/B27/B28/B66/B85

LTE-NB2 frequency bands (LTE-FDD)

B1/B2/B3/B4/B5/B8/B12/B13/B18/B19/B20/B25/B28/B66/B71/B85

EGPRS frequency bands

850/900/1800/1900 MHz

Network priority

4G (LTE-M1 or LTE-NB2), fallback to 2G (EGPRS)

4G transmit power

≤0.2 W

2G transmit power

≤2 W

SIM

Internal SIM + external Micro-SIM

Antenna connector

SMA connector / 50 Ω

Remote data destination

Web portal or FTP server

 

 

Data Logger – Memory

Memory type

Non-volatile Dataflash

Memory capacity

8 MB

Storage capacity

≥800,000 measured values

 

 

Data Logger – Time

Time accuracy with Internet synchronization

≤±4 s/month

Internet time synchronization

Once daily

Time accuracy without Internet synchronization

≤±2 min/month

Frequency standard

Quartz

 

 

Environmental Conditions

Ambient temperature

−20…+60 °C

Li-ion battery charging temperature (A1)

0…+45 °C, internally limited

Ingress protection

IP68 (EN/IEC 60529)

Submersion depth

≤3 m

Submersion pressure

≤0.3 bar

Climate class

4K4H (EN/IEC 60721-3-4)

Shock resistance

15 g (11 ms), EN/IEC 60068-2-27

Vibration resistance

4 g (10…2000 Hz), EN/IEC 60068-2-6

Electromagnetic compatibility (EMC)

Equipment Class B / Industrial Environment (EN/IEC 61326)

Operating altitude

2,000 m above sea level

Mean time to failure (MTTF)

258 years

Weight

0.9 kg

 

 

Materials

Materials in contact with the process

PA, aluminium/paint, PES, PUR, brass, nickel, silicone, NBR

 

 

Mechanical

Housing design

In-pipe housing (R2)

Housing diameter

Ø 48 mm

Overall length

439 mm

Mounting flange diameter

Ø 57 mm

Installation pipe size

From 2"

 

 

Sensor Connectivity

Maximum number of connected sensors

5

Maximum number of measured variables

11

Compatible sensor types

Level probes, ultrasonic sensors, radar sensors and similar level measurement sensors

 

 

Alarm Management

Alarm functions

Flooding and low water level alerting

 

 

Compliance

RoHS Directive

2011/65/EU

Battery Regulation

(EU) 2023/1542

Radio Equipment Directive (RED)

2014/53/EU

Drawing

HLF4 Autonomous Data Logger for Water Level Monitoring Drawing

Downloads

Hydrolog-HLF4 Datasheet DownloadHydrolog-HLF4 Datasheet
Hydrolog-HLF4 User Manual DownloadHydrolog-HLF4 User Manual
Hydrolog-HLF4 CE Declaration of Conformity DownloadHydrolog-HLF4 CE Declaration of Conformity